01 / MAIN ENGINE CIRCUIT AND HEAT PATH
Main engine circuit and heat path
The DMS 2024 screenshot identifies ID33 as the main engine HTFW cooling system. It shows two pump symbols, an HTFW cooler connected to LTFW System 31, a jacket water heater, a fresh water generator, an expansion tank and a deaerating tank. These are visible model features; their service conditions require further checking. The DMS 2017 manual separately documents main engine HTFW preparation and LT supply to the HT cooler. [1, 4]
For the central cooling arrangement considered here, engine heat passes from jacket water to LT fresh water at the HT cooler, then to sea water at the central cooler. HT, LT and sea water follow separate fluid paths. Figure 1 explains this heat path without reproducing the simulator piping diagram. Other vessel arrangements exist, so this is a selected system boundary. [3]
The fresh water generator and heater also matter when defining a test. Record whether heat recovery or preheating is active, rather than assigning every temperature change to the HT cooler.
Examine the authentic simulator screenEnlarge image ↗Figure 2. Authentic ID33 screenshot, DMS-2024A-2D V1.0, simulator time 00:00:20. The 36.0 °C indication and zero speed and flow indications describe this snapshot; they do not establish operation under load. Source Nikolaos Diakakis, 25 October 2026. [4]
02 / CIRCULATION AND THERMAL RESPONSE
Circulation and thermal response
A running indication alone does not establish adequate circulation. Pump duty depends on the pump and system characteristics; pressure must therefore be interpreted alongside available flow information and valve configuration. Record pump identity, status, measurement location and units. A discharge pressure without suction pressure cannot by itself establish pump differential pressure. [5]
A useful physical check is the steady heat balance across a defined water passage. Heat transfer rate is approximately mass flow rate multiplied by specific heat capacity and the water temperature change. This assumes negligible heat loss to the surroundings and negligible energy storage over the measurement interval. Use inlet and outlet measurements for the same passage and matched time intervals.
At comparable heat input, reduced mass flow can increase the engine water temperature rise. During a transient, however, the engine metal and water store energy, while control action and changing load affect the response. A larger temperature difference is therefore evidence to examine, not a diagnosis of pump failure. Compare engine inlet and outlet trends with HT cooler temperatures and LT supply conditions before selecting a cause.
Steady heat balance
Positive heat rate means heat gained by the water in the defined passage. With mass flow in kg/s, specific heat in kJ/(kg K) and temperature difference in K, heat rate is in kW.
03 / TEMPERATURE CONTROL AND PREHEATING
Temperature control and preheating
A temperature control study must identify the controlled variable, sensor location, target and actuator. A cooler bypass changes the share of water passing through the cooler; its actual control arrangement must be verified on the model. Preheating is a separate operating condition in which heat is added to prepare or maintain the engine temperature. It should not be assessed as though the engine were rejecting heat under load.
In general PID terminology, a controller compares a measured process variable with a setpoint and calculates an output command. [6] Figure 3 shows the DMS PIDController displaying SV 68.0, PV 36.00, DEV 32.00 and OUT 0.00, with Auto selected. These are snapshot readings. They do not establish normal operating limits, successful control or a fault. The earlier ID33 screenshot also shows LDCL State Automatic and an AUTO field of 65.00; the relationship between those displays remains to be verified. [4]
Confirm the loop mapping, signal scaling, valve action and any available position feedback before interpreting OUT. A command is not proof of valve position or branch flow. No controller tuning values are recommended here; response assessment needs a documented operating condition and a time record.
Examine the controller indicationsEnlarge image ↗Figure 3. Authentic PIDController screenshot, DMS-2024A-2D V1.0, simulator time 00:01:31. Auto is selected. Source Nikolaos Diakakis, 25 October 2026. [4]
| Visible label | Displayed value | Reading context |
|---|---|---|
| SV | 68.0 | Displayed target; not an approved operating limit |
| PV | 36.00 | Displayed measured value; sensor mapping to verify |
| DEV | 32.00 | Displayed deviation; control algorithm not established |
| OUT | 0.00 | Displayed output; not verified valve position or flow |
Values are transcribed as shown, without assigning units or scaling that the dialog does not establish. P, I and D settings are visible in the image but are not proposed as tuning values.
04 / PROPOSED INVESTIGATION AND SIMULATOR EVIDENCE
Proposed investigation and simulator evidence
The two supplied screenshots document DMS 2024A 2D V1.0. They show a zero speed indication and several zero flow indications, not a demonstrated trial under load. The DMS 2017 manual provides reference documentation; similarity does not establish identical controls, limits or fault functions in the installed version. [1, 4]
For a future investigation, first agree a reference condition, engine load, active heat recovery and control modes. Verify which measurements and disturbance mechanisms the model actually supports. Begin each comparison from approximately the same initial engine load and thermal condition. Apply one documented mechanism at a time, with agreed stopping and restoration criteria.
Record synchronised engine inlet and outlet temperatures, pump status, available pressure and flow, HT cooler temperatures, LT supply temperature, controller target, measured value and output. Include the disturbance and every intervention on the same timeline. Compare hypotheses involving heat input, circulation, LT heat rejection and control response. State which observations support each explanation and where missing measurements prevent discrimination. This is a proposed method; no experimental results or measured performance improvements are claimed.
| Record field | Required context |
|---|---|
| Time | Common simulator timeline and disturbance time |
| Measurement | Tag or location, value and unit |
| Operating state | Load, pumps, heat recovery and control mode |
| Intervention | Action, time and observed response |
05 / TECHNICAL COLLABORATION
Technical collaboration
We invite marine engineers, maritime institutions and simulator developers to review the circuit interpretation, measurement plan and terminology. The immediate contribution sought is technical scrutiny of the proposed method and confirmation of the installed model behaviour. This can help turn an educational example into a reproducible technical investigation.
Before a joint pilot, partners would agree responsibilities, reference conditions, supported disturbances, data permissions and the form of the report. The report should preserve the model version and operating context, distinguish observation from interpretation, and document unresolved discrepancies. A useful outcome is a defensible explanation of a thermal response, including its limits, rather than an assumed universal procedure. We can then assess whether the method transfers to another simulator or vessel arrangement and what must change.
TECHNICAL TERMINOLOGY
Terms used in this study
HTFW and JCW describe related cooling terminology; the exact circuit boundary remains installation specific.
- High temperature fresh water HTFW
- Fresh water in the higher temperature cooling circuit.
- Jacket cooling water JCW
- Cooling water serving engine cylinder components.
- Jacket water cooler
- Exchanger transferring jacket water heat to another circuit.
- Temperature control valve
- Valve regulating flow distribution to influence temperature.
- Cooler bypass
- Flow path around the cooler heat transfer passage.
- Expansion tank
- Tank accommodating changes in cooling water volume.
- Preheating
- Heat addition before operation or to maintain readiness.
- Temperature trend
- Temperature observations arranged against a common time reference.
- Process variable PV
- Measured quantity supplied to the control loop.
- Controller output
- Calculated command sent towards the actuator.
REFERENCES
Sources and documentation
- [1]
DMS 2017. Manual_Model_VLCC_7S80ME.docx. Cover date 30 November 2024. Section 2.7.3, printed pp. 32–33 (document pp. 61–62), and section 3.7.2, printed p. 118 (document p. 147). Reference manual.
- [2]
Everllence (June 2026). Efficiency improvements: Main engine auxiliary systems. 5510-0201-02, section 3, p. 12, Figures 4–5. Generic manufacturer arrangement; not validation of DMS parameters.
Read the manufacturer reference - [3]
Alfa Laval. Heating and cooling in the engine room. Central cooling and heat recovery.
Read the manufacturer reference - [4]
Diakakis, N. (25 October 2026). Two screenshots of DMS-2024A-2D V1.0: ID33 and PIDController. Simulator times 00:00:20 and 00:01:31. Reproduced unchanged in Figures 2 and 3.
- [5]
Grundfos. How to read a pump curve. Pump performance, system characteristics and duty point.
Read the manufacturer reference - [6]
NI (7 March 2025). The PID Controller and Theory Explained. General control terminology, not DMS implementation or tuning.
Read the technical reference
Public references checked on 26 October 2026.