It draws on the DMS-2017A system screen and the Greek handbook by Nikolaos Diakakis and Efstathios Zogopoulos. The diagnostic scenario is proposed for investigation; it is not a report of a newly recorded simulator trial. [1, 2]
01 / SYSTEM CONTEXT
How the seawater cooling circuit works
The heat path
In a central cooling arrangement, circulating fresh water carries heat from machinery to the central coolers. Sea water receives that heat across the heat-transfer surfaces and returns to the sea. The two fluids normally remain separate. Sea-water inlet conditions and the flow available through the coolers therefore affect the cooling available to the fresh-water circuit. [3]
For the fresh-water circulation and temperature-control side of this heat path, see the Low Temperature Fresh Water Cooling study.
The documented model
The ID30 screen shows high and low sea-chest connections, three labelled main cooling sea-water pumps and two central fresh-water coolers. Other branches are also visible, so the display should not be treated as an isolated pair of coolers. The model manual identifies sea-water preparation at ID30 and low-temperature fresh-water preparation at ID31. The number of pumps and coolers required in service must follow the documented configuration and cooling demand. [1, 2]
Sea chests and seawater strainers
Sea chests provide the hull intake to the seawater system. Strainers retain solid debris before it reaches downstream equipment. Their condition affects resistance in the flow path; any measured differential pressure must be interpreted at a stated flow. [3, 4]
Seawater cooling pumps
The pumps provide the head needed to circulate seawater against the resistance of the selected flow path. Delivered flow depends on pump characteristics and the system configuration. The three pumps shown are installed units; their presence does not establish how many must run in every operating condition. [1, 2, 5]
Central fresh-water coolers
In the central coolers, heat passes from the fresh-water circuit to seawater across separating surfaces. Normal heat transfer does not require the fluids to mix. Seawater flow, inlet temperature and the condition of the heat-transfer surfaces all influence cooling performance. [3, 6]
02 / HYDRAULIC AND THERMAL EVIDENCE
Monitoring seawater flow and heat transfer
Running status and hydraulic performance
A running indication establishes an equipment state, not the delivered cooling flow. Record suction and discharge pressures at identified locations, together with any available flow indication. Interpret them against the relevant pump curve and system configuration. Discharge pressure alone cannot establish that the required flow is reaching the coolers; pump head and flow are related through the pump and system characteristics. [5]
In a physical installation, cavitation can develop where local absolute pressure falls below the liquid's vapour pressure at its temperature. Vapour bubbles then form and can collapse as pressure recovers. Air entering the suction line is a different mechanism. Use either explanation in this study only if the installed simulator represents it and provides relevant evidence. [7]
The thermal link
For approximately steady operation, with negligible heat losses to the surroundings, the sea-water side can be examined using:
Q̇ is the heat-transfer rate in kW, ṁ the sea-water mass flow rate in kg/s and cp the specific heat capacity in kJ/(kg·K). The temperature difference is in K. It has the same numerical value as a difference expressed in °C. Both temperatures must refer to the same cooler and the same fluid.
Interpreting a temperature trend
At fixed heat duty and approximately constant cp, lower mass flow would require a larger sea-water temperature rise. During an actual disturbance, however, heat duty and stored thermal energy may also change. A temperature difference therefore needs a time reference and operating context. Compare the sea-water trend with the fresh-water temperatures, machinery load and any temperature-control behaviour represented by the model. A single temperature difference does not identify a unique fault.
03 / PROPOSED INVESTIGATION
Investigating reduced sea-water flow
Establish a reference condition
The proposed investigation concerns reduced sea-water flow through the central coolers at approximately unchanged initial machinery load. Before introducing a disturbance, establish and document a suitable reference condition in the simulator. Record the selected sea-chest route, pumps and coolers in service, fresh-water circulation, machinery load and any active model controls. This reference condition is to be established for the investigation; the published screenshot is not used as proof of an independently validated normal operating condition.
Represent one defined disturbance
Use a documented model fault or other supported simulation mechanism only after confirming how it changes the cooling circuit. The proposal does not assume that the installed DMS version includes a specific strainer-blockage or cooler-fouling function. Define the disturbance, the variables intended to remain unchanged and the observation period before a run. Instructors and technical reviewers should agree the model boundaries and restoration condition. This is a simulator investigation, not a shipboard switching or maintenance procedure.
Record the sequence
Use synchronised observations from ID30 and ID31, supported by other relevant model pages where required. Capture the simulator time, equipment state and available pressure, flow and temperature trends. If fresh-water temperature control and available cooling capacity cannot compensate for the disturbance, a rise in fresh-water outlet temperature is a hypothesis to test. Its occurrence, magnitude and delay must be measured rather than assumed.
04 / ALTERNATIVE EXPLANATIONS
Seawater cooling faults: comparing possible causes
Intake or strainer restriction
Examine suction conditions and any pressure difference available across the strainer. A strainer pressure drop is meaningful only with its measurement locations and flow conditions identified. Seek evidence for a restriction rather than inferring it solely from a cooling alarm. Apply this interpretation only where the model exposes the necessary measurements. [4]
Reduced heat-transfer performance
Maintained flow does not guarantee maintained thermal performance. Compare cooler inlet and outlet temperatures on both sides at comparable loads and sea-water inlet conditions. Fouling is one possible physical explanation for deteriorating performance, but a simulator conclusion must also identify which heat-transfer effects its model represents. A warmer fresh-water outlet alone does not prove fouling. [6]
Changed boundary conditions
A higher machinery load or warmer incoming sea water can change the thermal result without a new pump fault. Compare these conditions with the reference record before assigning a cause. If several variables change together, explain how this limits the comparison.
Measurement and configuration consistency
Check the identity, units and timing of each indication. Distinguish a pump-state change from a hydraulic response and a temperature response. Confirm the flow path and relevant controls against the model documentation. Treat unavailable measurements as limits on the conclusion, rather than replacing them with invented values or universal acceptance thresholds.
05 / REPORTING AND CONCLUSIONS
Make the reasoning open to review
What a completed investigation should report
A useful report states the model version, initial conditions, disturbance mechanism, observation interval and restoration criterion. It presents the time-linked indications and explains which observations support or challenge each hypothesis. A recovery time is meaningful only when its start and end conditions are defined. The number of alarms, the running indication or one final temperature is not sufficient to establish a successful technical diagnosis.
The engineering conclusion
Cooling performance is a system result. Sound analysis connects the available sea-water path and hydraulic behaviour with heat transfer and the response of the fresh-water circuit. The educational value lies in making that reasoning visible and open to review. The screenshot documents a system arrangement; reproducible run records would be needed to evaluate the proposed scenario and its outcomes.
TECHNICAL TERMINOLOGY
Terms used in this case
- Sea chest
- A sea-water intake chamber in the hull.
- Sea-water strainer
- A component that retains solid debris from the water.
- Central fresh-water cooler
- A heat exchanger transferring heat from fresh water to the cooling medium.
- LTFW
- Low-temperature fresh water.
- Suction pressure
- Pressure at an identified point on the inlet side of a pump.
- Discharge pressure
- Pressure at an identified point on the outlet side of a pump.
- Mass flow rate
- Mass passing a section per unit time, for example kg/s.
- Heat duty
- The rate of heat transfer, expressed here in kW.
- Overboard discharge
- The outlet path returning water to the sea.
- Reference condition
- A defined operating condition used for comparison.
REFERENCES
Sources and documentation
- [1]
Diakakis, N. and Zogopoulos, E. (2026). Ψηφιακό μηχανοστάσιο και διαχείριση ναυτικών συστημάτων. Volume A. 24grammata. Section 5.8, Figure 5.2, pp. 151–152.
Greek-language book excerpt · PDF - [2]
DMS-2017. Marine Engine Room Simulator Manual. Cover date 30 November 2024. Sections 2.2.3 ID30 and 2.2.4 ID31, printed pp. 6–7.
- [3]
Alfa Laval. Heating and cooling in the engine room. Central cooling system.
Read the manufacturer reference - [4]
Grundfos. Strainer. Pressure-drop monitoring across a strainer.
Read the technical reference - [5]
Grundfos. Pump curves. Flow, head and system characteristics.
Read the technical reference - [6]
Alfa Laval. Troubleshooting for plate heat exchangers. Performance issues.
Read the manufacturer reference - [7]
Grundfos. Cavitation in pumps.
Read the technical reference
Web references checked on 6 November 2026.